Memo-Graph S 5 Operation / adjusting device settings - Set-up to commissioning
Endress+Hauser 45
Signal settings: Analogue outputs (option) sub-menu
Settings only required if analogue outputs are to be used.
Signal settings: Digital outputs (Relays/OC) sub-menu
Defining operating mode of the integrated relays or the open collector output.
Set-up -> Signal settings -> Analogue outputs -> Analogue output x
Output signal Can be selected per channel. See also “Connections / terminal diagram”
Reference channel Here, the input channel that is to be changed is selected.
Input signal
Measuring range start
Measuring range end
Can not be edited
4 mA correlate Lower range for the output value
Enter the lower input value that corresponds to the output value here.
20 mA correlate Upper range for the output value
Enter the upper input value that corresponds to the output value here.
Set-up -> Signal settings -> Digital outputs (Relays/OC)
Relay 1 in LV Function of the relay in case of a limit value, i.e. when it is activated.
Closing: in case of LV connections 41-44 are shorted, in idle status connections 41-42.
Opening: in case of LV connections 41-42 are shorted, in idle status connections 41-44.
! Note!
In this operating mode, the relay coil is energised in normal operation, i.e. you can also use it as a message for a power
failure since it then reports “limit value” or power failure by shorting contacts 41-42 (“Maximum safety”).