5 Operation / adjusting device settings - Set-up to commissioning Memo-Graph S
28 Endress+Hauser
Basic settings: Operating modes sub-menu
Settings that determine the functions of the device.
Time NT -> ST Time at which the time is moved forward by 1 hour on the day of the changeover from normal time to summertime.
Format: hh:mm
Date ST -> NT Day in autumn on which the changeover from summertime to normal time takes place.
Format: DD.MM.YY
Time ST -> NT Time at which the time is moved back by 1 hour on the day of the changeover from summertime to normal time.
Format: hh:mm
Release code Ex works: “0000”, i.e. device can be set at any time without release code.
Individual code set: device can only be set after entering this code.
! Note!
Make a note of the code and store it somewhere where it is inaccessible to unauthorised persons.
Temp. unit Selecting the temperature unit. All directly-connected temperature measurements with thermal elements or resistance
thermometers are displayed in the defined unit.
Text thickness Defines in which line thickness the analogue signals are recorded (normal =1 point with thin text; bold = 2 points with
wide text).
Set-up -> Basic settings
Set-up -> Basic settings -> Operating modes
Open circuit The directly-connected thermal elements and resistance thermometers can be monitored for breaks in cycles by an
impressed current. This monitoring can be switched on or off here.
Open circuit value Selection: lower limit stop or upper limit stop.
Measured value that is set for the graphic display when an open circuit is detected.
Jump in the signal recording on lower or upper display range.
Limit values “Product-related”: the limit value monitor is only active when a product is running.
“Channel-related”: the limit values are only effective from the measured signals, therefore independent of a product run.
ATA operating mode “Stack memory”: if the ATA flash card is full, no further storage onto this card can be carried out until it has been read
out and deleted or replaced with a new card.
! Note!
In order to avoid data loss or to switch a relay, further settings can be made under “Data carrier full” for this case.
“Ring memory”: if the ATA flash card is full, the oldest data is always deleted in order to make room for new data.